GR93 Controller GR 93

  • PDF

General Characteristics

Possible types of regulations: - ON-OFF - Pl (proportional and integral) - PIQ (proportional, integral, and directly proportional to flowrate). The PIQ adjustment represents an important novelty inasmuch as it allows an immediate intervention to be made for the intake of the chemicals upon any change of liquid flowrate, without waiting for the analyzer's return signal. A metering can also be made proportional only to the flowrate (IF). Moreover, by associating the operating threshold with one of the two other thresholds (MAX or MIN), a hysteresis-based ON-OFF type adjustment may be made as well. The proportional parameter "P" may range from 0% fo 400% and the integration time "I" from 1 and 20 minutes. The flowrate parameter "Q" is directly related to the metering level. The regulation is typically performed by using the 4 -:20 mA analog output which governs the self-regulating metering pump (4 mA = 0% flowrate; 20 mA = 100% flowrate), but the ON-OFF output may be used as well, which allows a PWM to be carried out over a time which is generally of 60 seconds. The calibration of the unit can be performed by entering data relevant to two characteristic points of the measurement range. Should these data be not easily available, the use of an automatic calibration system based on stored-in-memory average parameters would be in order.

 

 

 

Software Versions and Specifications for
GR 930 GR 931 GR 934 GR 936 GR 937 GR 938
click on the desired item

A little adjustment is also possible upon only one measuring point.
All the above operations can be easily carried out and verified by using the display-aided push-button panel. The GR 93 is provided with a user-friendly three-key menu, one key being for the operating mode, and the others (+ and -) allowing parameters selection. The RS 232 port (available on request) is particularly useful for:

  • connecting the unit with a PC for controlo and operation purposes;
  • connecting the unit with a PC in order to re-program it by means of our dedicated software;
  • connecting the unit with remote control systems via a modem either on a telephone line or wireless.

The following names of versions are composed from the name of the hardware (for example GR 93) and the version of the software (for example 2) to obtain the full name (for example GR 932)

General Specifications

  • Inputs / Outputs optoisolated
  • Display LCD alphanumeric, back illumination, 32 character x 2 linees
  • Display LCD alphanumeric, back illumination, 32 character x 2 linees
  • Interface RS 232 (optional)
  • Power supply: 230V a.c. 50/60Hz (other volatge on request)
  • 1 fuse (on phase)
  • Absorbtion: 10W
  • 4-20 mA input resistence: 50 ohm
  • Max resistence applicable to 4-20 mA inputs: 200 ohm
  • N.O. contacts holder: 24V 1A max
  • Front dimension: 72 x 144 x 145 (depth) mm
  • Weight: 0.8 kg approx.
  • Protection IP 20
  • EMC - EMI cortified for industrial environment.
GR 930 - Versione 0
Control Function:

Controller with possible configuration.

Measurements: Free
Features:
  • Selection of measurements to be displayed (1)
  • Selection of measurement range (1)
  • Possibility of entrerimg temperature-compensing curve of the analysis(1)
Specifications:
  • 3 analog 4-20 mA optoisolated inputs (analysis + temp. + flowrate)
  • 1 analog 4-20 mA optoisolated inputs feedback from self-regulating
  • pump (e.g. PD series pumps with AR optional)
  • 2 analog 4-20 mA output (pump flowrate + analysis)
  • 3 intervention thresholds (operational, alarm for min., alarm for max.)
  • 2 ON-OFF relay outputs (1 for alarm max.+min.+self-regulator failure and 1 for PWM with TPWM = TINT x 2 sec.)
  • predisponition for RS 232 interface
*Parameters factory-preset or programmable throgh RS 232 port by dedicated software.
GR 931 - Versione 1
Control Function:

Threshold-operated ON - OFF

Measurements:

pH or Redox or Residual chlorine or Conductivity

Specifications:
  • 2 analog 4-20 mA optoisolated inputs (analysis + temp.)
  • 1 analog 4-20 mA output (calibrated analisys)
  • 3 intervention thresholds (operational, alarm for min., alarm for max.)
  • 2ON-OFF relay outputs (operational, alarm for min. and max.)
  • predisponition for RS 232 interface

pH and conductivity measurements are temperature -compensed.

GR 934 - Software Version 4
Control Function:

PI or PIQ (directly proportional to flowrate)

Measurements: pH
Specifications:
  • 3 analog 4-20 mA optoisolated inputs (pH +Temp + Flowrate)
  • 1 analog 4-20 mA optoisolated inputs (feedback from self-regulating pump with AR optional)
  • 2 analog 4-20 mA optoisolated output (calibrated analisys + pump flowrate)
  • 2 alarm thresholds (min. and max.)
  • 1 operational threshold (either PI or PIQ)
  • 2 ON-OFF relay outputs (1 for alarm max.+min.+self-regulator failure and 1 for PWM with TPWM = TINT x 2 sec.)
  • predisponition for RS 232 interface

Tpwm= period of pulse wave modulation
Tint= integration time parapeter of PI or PIQ settings

GR 936 - Version 6
Control Function:

Controller/Curve-linerizing unit. Particulary useful for channel flowrate measurements (include the counter).

Measuremnts:

Dissolved oxigen

Features:
  • Selection of measurements to be displayed (1)
  • Selection of measurement range (1)
  • Possibility of entrerimg an output versus input curve (1)
  • Possibility of entering a linearized output/input ratio (1)
Specifications:
  • 1 analog 4-20 mA optoisolated inputs (e.g. channel level)
  • 1 analog 4-20 mA optoisolated inputs (feedback from self-regulating pump with AR optional)
  • 2 analog 4-20 mA output (pump flowrate + analysis)
  • 1 intervention thresholds (operational, alarm for min., alarm for max.
  • 2ON-OFF relay outputs (1 for alarm max.+ min.+self-regulator failure and 1 for PWM with TPWM = 60 sec.)
  • predisponition for RS 232 interface
*Parameters factory-preset or programmable throgh RS 232 port by dedicated software.
GR 937 - Version 7
Control Function:

PI or PIQ (directly proportional to flowrate) or IF

Measurements:

Residual chlorine

Specifications:
  • 2 analog 4-20 mA optoisolated inputs (analysis + Flowrate)
  • 1 analog 4-20 mA optoisolated inputs (feedback from self-regulating pump with AR optional)
  • 2 analog 4-20 mA optoisolated output (calibrated analisys + pump flowrate)
  • 2 alarm thresholds (min. and max.)
  • 1 operational threshold (either PI or PIQ)
  • output/input ratio (IF only)
  • 2 ON-OFF relay outputs (1 for alarm max. + min. + self-regulator failure and 1 for PWM with TPWM = 60 sec.)
  • predisponition for RS 232 interface
GR 938 - Version 8
Measurements:

Dissolved oxigen

Specifications:
  • Calibration automatic in atmosphere
  • 2 analog 4-20 mA optoisolated inputs (analysis + temp.)
  • 1 analog 4-20 mA optoisolated inputs (feedback from self-regulating blower)
  • 2 analog 4-20 mA output (blower control + analysis)
  • 3 intervention thresholds (operational, alarm for min., alarm for max.)
  • 2 ON-OFF relay outputs (1 for alarm max.+min.+self-regulator failure and 1 for PWM with TPWM = TINT x 2 sec.)
  • predisponition for RS 232 interface